To identify the cause of a long
term intermittent fault at a large pumping station, which is
unattended for most of the year. Once a year the starting circuit
would fail causing downtime, damage and costly repair.
The starting circuits for properly sequencing the
startup of six large water authority pumps, and for distributing load
between the pumps, is complex. Periodically the starting circuits would
fail, causing damage, downtime, and frustrated irrigators and consumers.
A dataTaker 500 was used to monitor current transducers
connected to various points through the startup circuitry. Data was stored
into a circular buffer, such that at any time the most recent 7 days
of data was available. The dataTaker had effectively become a "flight
recorder".
When the fault next occurred, data for the recent
period revealed that the starting circuit had attempted to start two
pumps almost simultaneously.
Costly plans to redesign the whole pumping system were
shelved.
|